Master Alarm Conversion Kits
Master Alarm Conversion Kits are a set of components that can be used to modify or upgrade an existing medical gas master alarm system. Medical gas alarm systems are designed to monitor the presence and concentration of various gases in a healthcare facility, such as oxygen, nitrogen, carbon dioxide, and nitrous oxide. These gases are used for a variety of medical purposes, including respiratory support, anesthesia, and pain management. The purpose of a conversion kit is to allow the medical gas alarm system to be compatible with new types of gas sensors or to perform additional functions. For example, a conversion kit might include new sensors that can detect additional gases, or it might include software and hardware upgrades that allow the system to communicate with other devices or building management systems.
Tri-Tech Medical master alarm panels are designed with state of the art technology for the utmost in safety and reliability.
- Up to 128 alarm points per panel (8 points per circuit board)
- Alarm points may be programmed individually, NC or NO or Disabled
- Datafile of NFPA 99 alarm labels pre-loaded into each board
- Design options available to communicate with dry contact, transducer and 4 - 20 mA sensors
- Wireless master alarms available
- Built-in history feature
- Five year parts and one year labor warranty
Master Alarm Panels Product Video:
Features of Master Alarm Systems
The Tri-Tech Master Alarm Panel monitors and displays normal and alarm conditions from up to 128 remote medical gas source signals. Pressure switches and DISS union check valve connectors are sold separately.
- ETL listed to UL-1069 and CSA-C22.2 No. 205
- Complies with NFPA 99
- Manufactured & Tested in the U.S.A. with Domestic & Imported Components
- Individual 2.85" LCD touch screen display for each 8 dry contact or 8 transducer board or for each 2 4 - 20 mA boards
- Emergency preparedness instructions may be input for each alarm signal and will be displayed during an alarm event
- Optional Ethernet board (may be added after installation) provides; text or email notification to 5 mobile devices of an alarm event, website with real-time graphic of alarm panel status with access to event logs, event log for up to 1,000 events, modbus interface gateway for communication with facilities building management system.
- Optional BACnet interface gateway for communication with facilities building management system.
- Self-diagnostic (test button) and error message display for ease of maintenance.
- Audio and visual alarm indicators
- Bright easy to read L.E.D. displays – clearly visible in both day and night lighting conditions
- Visual (green) indication of normal condition
- Constant display and monitoring of each source alarm signal
- Individual user programmable remote signal alarm points (NC, NO or disabled)
- Dry contacts for remote monitoring of all alarm conditions
- Alarm history display of previous alarm conditions
- Hinged frame with lanyards for easy accessibility